The design of the UV sensor ensures that the flame detector will not react to the background radiation from hot refractory or any other source of infrared light. The UV-flame detector is equipped with an optical interface that visibly displays the intensity of the flame signal. Connects directly to the ionization or LDR input of the control box. Operations are to be in a closed area.
- Input: 120 VAC; 50/60 Hz; Amp Consumption: 5.5 mA
- Restart Time: >5 seconds (between burner shut down and renewed start-up)
- FET-Output:
- Switch-On delay: 0.5 seconds
- Switch-Off delay: <0.5 seconds
- Maximum Switched Current; Power; Voltage: 15 mA; 0.3 W; 280 VAC/400 VDC
- Optical features:
- Spectral range: 185-260 nm
- Acceptable loss of flame signal ca.: 200ms
- Adjustment: Radial, left, optional axial (reduced sensitivity at approximately 40%)
- Lifetime of UV-tube: >10,000 hours
- Operating Temperature: -4° – 140°F (-20 °- 60°C)
- Temperature >120°F reduces the lifetime of the UV-tube
- Humidity: 95% (maximum), no condensation permitted
- Protection: IP41
- Operation Position: Any
Agency Listing: UL